This equipment is a counterflow heat exchanger for cooling
of boiler water , feet , steam , chemical solutions and
other fluid samples at high temperatures.
The cooler is used on the liquid sampling panel.
The following equipment could be also supplied by FAP in
order to complete the complete the sampling equipment:
CO2 Scrubber
Caution Exchanger Vessel (including resin)
Simplified Cubicle (enclosure of sampling rack)
Press Reducer & Safety Valve
Thermometer & Pressure Indicator
Flow Indicator & Flow Meter
Analyzaer & Transmitter
Simplified Cubicle (enclosure of sampling rack)
Heater and Controller (for cubicle)
PROCESS DATA for BOILER SAMPLING
DESCRIPTION
UNIT
DEFAULT
REMARKS
Sampling
fluid
Steam /
water
Tube
Side
Sampling fluid inlet Temp.
°C
450
max.550
Sampling
fluid Outlet Temp.
°C
max.50
Sampling fluid Inlet
pressure
barg
max.150
Sampling
fluid capacity
Lit/hr
max.60
Cooling fluid
Water
Cooling
fluid Inlet temperature
°C
30.0
max.40
Cooling fluid Inlet pressure
barg
8
Cooling
fluid capacity
Lit/hr
2400.0
Heat exchanger type
Coil
Coil
theoretical proof design pressure
barg
max.400
Coil design temperature
°C
max.550
Shell
design pressure
barg
max.50
Shell design temperrature
°C
100
Heating
surface
m2
0.5
Shell material
A240 - TP 304L
Eq. SUS 304L
Tube
A 312 -
TP 316 L
Eq. SUS
316 L
Pressure and material will be finalized by FAP based on