  SAMPLING COOLER
 
                    
  Function:
  This equipment is a counterflow heat exchanger for cooling of boiler water , feet , steam , chemical solutions and other fluid samples at high temperatures.
The cooler is used on the liquid sampling panel.
   
  The following equipment could be also supplied by FAP in order to complete the complete the sampling equipment:
  CO2 Scrubber
  Caution Exchanger Vessel (including resin)
  Simplified Cubicle (enclosure of sampling rack)
  Press Reducer & Safety Valve
  Thermometer & Pressure Indicator
  Flow Indicator & Flow Meter
  Analyzaer & Transmitter
  Simplified Cubicle (enclosure of sampling rack)
  Heater and Controller (for cubicle)
   
  PROCESS DATA for BOILER SAMPLING
 
DESCRIPTION UNIT DEFAULT REMARKS
Sampling fluid   Steam / water Tube Side
Sampling fluid inlet Temp. °C 450 max.550
Sampling fluid Outlet Temp. °C max.50  
Sampling fluid Inlet pressure barg max.150  
Sampling fluid capacity Lit/hr max.60  
Cooling fluid   Water  
Cooling fluid Inlet temperature °C 30.0 max.40

Cooling fluid Inlet pressure

barg 8  
Cooling fluid capacity Lit/hr 2400.0  
Heat exchanger type   Coil  
Coil theoretical proof design pressure barg max.400  
Coil design temperature °C max.550  
Shell design pressure barg max.50  
Shell design temperrature °C 100  
Heating surface m2 0.5  
Shell material   A240 - TP 304L Eq. SUS 304L
Tube   A 312 - TP 316 L Eq. SUS 316 L
   
  Pressure and material will be finalized by FAP based on project.

  

 

 